Cause: Improper cooling, electric current to compressor is too high activating a protective switch Trouble shooting method: 1.Water level in cooling water tower is too low, raise water float height or increase water supply 2.Perform cleaning and maintenance on water tower and condenser 3.Air-cooled condenser is dirty.Please clean and perform maintenance Cause: Airflow is too small, freeze prevention switch will be activated Trouble shooting method: 1.Clean the air filter 2.Check the evaporator, if dirty, clean and perform maintenance 3.Excessive drag in air pipes, please increase pipe size or number of vents
|